Ammonia is a promising carbon-free marine fuel, but accidental leakage in enclosed engine rooms can generate persistent toxic clouds and severe breathing-zone exposure. Conventional ventilation assessment based only on nominal exhaust capacity or air-change rate may not adequately represent hood capture performance, particularly when the leak jet is not aligned with the suction region. In this study, eighteen transient three-dimensional CFD simulations were conducted for a full-scale ammonia engine-room test bed by varying leak location, hood type, and hood height. The results show that source-to-hood alignment strongly controls early plume capture and long-term residual contamination. The well aligned IE-T3-H6 case achieved a removal efficiency of 98.77% with only 0.05 kg NH3 remaining at 180 s, whereas the poorly aligned VALVE-T3-H6 case achieved only 38.30% removal and retained 2.51 kg NH3. In the worst case, the 30 ppm toxic cloud expanded to nearly the full compartment volume, and the breathing-zone average concentration remained above 30 ppm until approximately 913.5 s. These findings demonstrate that hood ventilation performance should be evaluated using toxic cloud volume, breathing-zone exposure, residual mass, and capture delay even under an identical exhaust-flow basis.
| Published in | Abstract Book of ICEER2026 & ICCIVIL2026 |
| Page(s) | 17-17 |
| Creative Commons |
This is an Open Access abstract, distributed under the terms of the Creative Commons Attribution 4.0 International License (http://creativecommons.org/licenses/by/4.0/), which permits unrestricted use, distribution and reproduction in any medium or format, provided the original work is properly cited. |
| Copyright |
Copyright © The Author(s), 2026. Published by Science Publishing Group |
Ammonia Dispersion, Ventilation Hood Efficiency, Computational Fluid Dynamic, Toxic Cloud Evolution, Breathing-zone Exposure, Toxic in the Engine Room